HVAC Control Systems Commissioning Log
1 · Control Systems Functionality Check
| 1 · Control Systems Functionality Check | Y | N | Notes | |
|---|---|---|---|---|
| 1.1 | All control panels are installed and energized | |||
| 1.2 | Control wiring is complete and free from damage | |||
| 1.3 | System responds to setpoint adjustments | |||
| 1.4 | Schedules and override commands are working correctly. | |||
| 1.5 | Interlocks operate in the correct sequence | |||
| 1.6 | Sequence of operations verified against design documents | |||
| 1.7 | Economizer/outside-air damper responds per sequence | |||
Photos - Control Systems Check · photo refs
2 · Sensor and Device Calibration
| 2 · Sensor and Device Calibration | Y | N | Notes | |
|---|---|---|---|---|
| 2.1 | Temperature sensors are reading within allowable tolerance | |||
| 2.2 | Pressure and humidity sensors are verified and labeled | |||
| 2.3 | Control valves stroke fully and respond to commands | |||
| 2.4 | Damper actuators operate as expected | |||
| 2.5 | Alarms trigger under fault conditions | |||
Photos - Sensor & Device Calibration · photo refs
3 · Trend Log Verification Table
Use this table to confirm that required system points are being trended correctly and data is logging as expected.
| System/Device | Control Point | Expected Range | Observed Value | Duration of Trend | Notes |
|---|---|---|---|---|---|








