An emergency light inspection checklist records whether a building's battery-backed emergency lights and exit signs are mounted, lit, charged and working, and what happened when they were tested. Facility staff, property managers and electrical contractors use it on a regular round, and the signed forms become the record a fire inspector or insurer asks to see.

What goes on an emergency light inspection checklist

The emergency light inspection form follows the order you'd work at each fixture or group of fixtures: look first, then test, then write up what failed.

SectionWhat you record
Visual inspectionFixtures mounted and unobstructed, lenses and covers intact, charging indicators on, EXIT text visible and lit, housing and wiring intact, with photos
Functional testingMonthly or annual test; whether all lights stayed on for 30 seconds (monthly) or at least 90 minutes (annual), with the annual test's start and end times
Condition and observationsMalfunctions or failures, repairs needed or done, a description of each failure, and whether a follow-up or re-test is needed and when
AttachmentsPhotos or files for the audit trail
Facility and equipment informationBuilding, address, area, floor or room, equipment ID or label, and fixture type: emergency light, exit sign or combination unit
Final sign-offOverall status (pass, pass but needs repair, or fail), next due date, inspector and supervisor signatures

Monthly and annual tests: what the standards say

The form's own notes point to two sources. NFPA 101, the Life Safety Code, at section 7.9.3, calls for a 30-second functional test of emergency lighting every month and, for battery-powered units, a 90-minute test once a year, with a written record of each test kept for inspection. OSHA 1910.37(b)(1) requires exit routes to be adequately lit. Your local fire code may adopt a specific edition or add its own rules, so check the current requirements with your authority having jurisdiction before you set the schedule.

Record both start and end times on the annual test rather than just ticking the box. A unit that lasts 70 minutes looks fine on a quick glance and fails the full-duration test, and the times are what prove the test actually ran.

How to run an exit light inspection

  1. Fill in the facility details and the equipment ID for each fixture or group, so failures can be found again.
  2. Walk the exit routes and do the visual checks: anything blocked, cracked, dark or hanging gets a No and a photo.
  3. Run the test, using the unit's test button or by cutting normal power to the circuit, and watch every fixture in the group.
  4. Write up each failure in plain words: fixture ID, what it did, what you think is wrong.
  5. Set the overall status, the follow-up date for repairs and the next due date, then sign.

A fixture marked "pass, but needs repair" is one that works today but won't for long: a cracked lens, a dim lamp, a loose mount. Give it a follow-up date so it doesn't stay on that list for a year.

Related forms

For the full test log on its own, use the emergency lighting and exit sign test form. The same round is a good time for a fire extinguisher inspection checklist.

Run it in Workyard or download it free

In Workyard, the checklist is a digital form your crew fills in on a phone at the building, with photos of failed fixtures and signatures on screen. A failed test can go straight to a named person for repair, and every submission is filed to the job in the office, ready to export as PDF or CSV. See inspection forms in Workyard. Or download the free template as a PDF, Word or Excel file.