Electrical Rough-In Inspection
1 · General Electrical Requirements
| 1 · General Electrical Requirements | Pass | Fail | N/A | |
|---|---|---|---|---|
| 1.1 | Approved Wiring Method: NEC-compliant for location/use. | |||
| 1.2 | Cable Support & Protection: NM/RMC/EMT supported correctly. | |||
| 1.3 | Box Fill: Adequate volume for conductor count. | |||
| 1.4 | Ground Wires Pigtailed: Per NEC 250.148. | |||
| 1.5 | Box Bonding: Metal boxes properly grounded. | |||
| 1.6 | Conductor Length: ≥6″ free conductor in each box. | |||
| 1.7 | Splices & Connectors: Made in boxes (NEC 300.15); listed, secure and rated for the conductors (NEC 110.14). | |||
| 1.8 | Panel Clearance: 30″W x 36″D clear in front of panel. | |||
| 1.9 | Other Criteria (describe below) | |||
Photos - General Electrical Requirements · photo refs
2 · Kitchen & Dining Areas
| 2 · Kitchen & Dining Areas | Pass | Fail | N/A | |
|---|---|---|---|---|
| 2.1 | Small Appliance Circuits: 2+ 20A circuits for kitchen/dining. | |||
| 2.2 | Countertop Receptacles: No point >24″ from an outlet. | |||
| 2.3 | Island/Peninsula Outlets: Receptacle, or provision for a future receptacle, per the adopted NEC 210.52(C). | |||
| 2.4 | GFCI Protection: All required outlets GFCI protected. | |||
| 2.5 | Lighting Outlets: Properly located and switched. | |||
| 2.6 | Dedicated Circuits Labeled: For microwave, dishwasher, etc. | |||
| 2.7 | Other Criteria (describe below) | |||
Photos - Kitchen & Dining Areas · photo refs
3 · Bathrooms, Laundry & Garage
| 3 · Bathrooms, Laundry & Garage | Pass | Fail | N/A | |
|---|---|---|---|---|
| 3.1 | Bathroom Circuit: 20A circuit for bathroom receptacles (NEC 210.11(C)(3)). | |||
| 3.2 | Bathroom GFCI: Installed and tested. | |||
| 3.3 | Outlet Near Sink: Within 3′ of basin. | |||
| 3.4 | Shower/Tub Clearance: No receptacle within 3′ horizontally and 8′ vertically of tub or shower (NEC 406.9(C)). | |||
| 3.5 | Laundry Circuit: 20A circuit present and labeled. | |||
| 3.6 | Garage GFCI: All receptacles protected. | |||
| 3.7 | Dryer/Range Cable Type: 4-wire connection present. | |||
| 3.8 | Plumbing Bonding: Water/gas bonded per NEC 250.104. | |||
| 3.9 | Other Criteria (describe below) | |||
Photos - Bathrooms, Laundry & Garage · photo refs